Product Center

LKRM16-12/24KV Eco-friendly Gas-Insulated Ring Main Unit


LKRM16-12/24KV Eco-friendly Gas-Insulated Ring Main Unit


Product Overview

 

The LKRM16-12/24 dry-air fully insulated and fully sealed gas-insulated ring main unit, manufactured by our company, is a new type of medium-voltage ring main unit that we have independently developed by absorbing advanced foreign technologies. This cabinet model is produced using state-of-the-art manufacturing equipment, including fully automatic laser cutting machines, CNC sheet-metal processing centers, fully automatic welding machines, and automated maintenance equipment for dry-air gas. Moreover, the application of various advanced testing instruments, flexible assembly lines, and CAD/CAM systems provides an effective guarantee of the high quality and reliability of the LKRM16-12/24 dry-air fully insulated and fully sealed gas-insulated ring main unit. The ring main switchgear adopts a modular design, perfectly combining fixed and flexible configurations to suit different application scenarios and provide tailored technical solutions that satisfy diverse user needs. The incorporation of sensor technology and the latest microprocessor-based protection devices, coupled with advanced technical performance and a lightweight, flexible assembly approach, ensures that this product can safely meet the ever-changing demands of the market.

 

Product Features

The inflatable switchgear uses dry air gas as the arc-extinguishing and insulating medium. The switchgear features a fully sealed, fully insulated structure. The enclosure is filled with dry air gas at an absolute pressure of 1.4 bar, achieving a protection rating of IP67.

Switchgear is divided into two categories: fixed-unit assemblies and expandable-unit assemblies.

The entire switching device is completely unaffected by external environmental conditions and can ensure normal operation even under extreme conditions such as brief immersion in water. The product requires no maintenance throughout its entire service life.

Switchgear typically features front-mounted incoming and outgoing lines, but can also be configured for side-outgoing lines or side extensions depending on the installation location.

The switchgear is equipped with a comprehensive “five-protection” interlocking system, completely eliminating the possibility of personnel and equipment malfunctions caused by human error.

The cabinet has a compact size, is easy to install, and is suitable for spaces with limited room and challenging environmental conditions.

Therefore, the switchgear is equipped with a reliable safety venting channel that can ensure the personal safety of personnel even under extreme conditions.

Switchgear can be equipped with electric, remote-control, and monitoring devices according to different user requirements.

 

Operating environment

Normal operating conditions

Ambient temperature

Humidity

Maximum temperature: +40℃

Maximum average relative humidity

Maximum temperature (24-hour average)

24-hour measurement ≤95%

Minimum temperature: -40℃

1-month measurement ≤ 90%

 

Special conditions

In accordance with GB3906 and IEC62271 standards, for special operating conditions that differ from normal operating conditions, the manufacturer and the end user must reach a consensus.

If the operating environment involves particularly harsh conditions, you must consult with the manufacturer and supplier.

When electrical equipment is installed at an altitude of 1,000 meters or higher, this must be specially noted so that the pressure can be adjusted during manufacturing.

 

Technical Parameters

Project

Unit

C module

F module

V module

Load switch

Combined electrical equipment

Vacuum switch

Isolation/Earthing Switch

Rated voltage

kV

12/24

12/24

12/24

12/24

Rated frequency

Hertz

50 

50 

50 

50 

Power-frequency withstand voltage

kV

42/65

42/65

42/65

42/65

Lightning impulse withstand voltage

kV

75/125

75/125

75/125

75/125

Rated current

A

630/630

Note 1

630/630

630/630

Breaking capacity

-

-

-

-

-

Rated closed-loop breaking current

A

630/630

630/630

630/630

-

Rated cable charging and breaking current

kA

10 

-

 

-

Rated short-circuit making current (peak)

kA

50 

80 

50 

-

Rated peak withstand current

kA

63/50

-

63/50

-

Rated short-time withstand current

kA/3S

25 

25 

25 

25 

Rated short-circuit breaking current

kA

-

Note 2

25 

-

Rated Transfer Current

A

One

1750/800

-

-

Maximum current for fuse use

A

-

125/100

-

-

Circuit resistance

microohm

≤300

≤400

≤200

-

Mechanical life

Next

5000 

5000 

10000 

3000 

Altitude

≤2000m

Dry air, dry air gas pressure

Below 20℃, it is 1.4 bar (absolute pressure).

Annual leakage rate

0.25% per year

Protection level

Dry-air chamber IP67; circuit breaker enclosure IP67; switchgear enclosure

Note 1) Depends on the fuse’s current rating.

Note 2) Subject to high-voltage fuse.