Product Center

Mobile Substation for Vehicles


Mobile Substation for Vehicles


Product Overview

 

The vehicle-mounted mobile substation consists of five main modules: the Hybrid Gas-Insulated Switchgear (HGIS) module, the main transformer module, the integrated automation module for switchgear cabinets, the medium-voltage distribution room module, and the equipment transportation module. Each module adopts an all-in-one prefabricated structure, enabling factory-based modular production of various functional units. During the prefabrication process, internal connections and debugging within each module are completed simultaneously. The overall structural design of the vehicle-mounted mobile substation is compact and highly mobile, allowing it to be put into operation within a short time. It boasts high power supply reliability, flexible operation, and simple, convenient assembly. Moreover, individual components can operate independently and be transported separately. The semi-trailer remains in a mobile standby state under normal circumstances; upon receiving a departure order, it can immediately set out and reach its designated destination within just a few hours, ready to connect to the power grid. This makes it particularly well-suited to meet power supply demands in scenarios such as technical upgrades of substations, equipment maintenance, temporary power supply at construction sites, emergency repairs following accidents, and situations arising from natural disasters.

 

Product Features

Mobile and flexible: The equipment is reliably integrated with the vehicle body, enabling rapid deployment to the scene.

Fast commissioning: rapid response, rapid deployment, and quick commissioning.

High adaptability: Featuring high structural strength and sophisticated shock-absorbing measures, suitable for a wide range of operating conditions.

Compact structure: Highly integrated design meets road transportation requirements.

 

Implementation standard

 

GB/T 17467-2020 "High-Voltage/Low-Voltage Prefabricated Substation"

GB/T 4208-2008 "Ingress Protection Ratings (IP Code)"

DL/T 537-2018 Guidelines for the Selection of High-Voltage/Low-Voltage Prefabricated Substations

DL/T 2821—2024 "Technical Specification for Prefabricated Modular Equipment in Substations – Part 1: Switchgear Enclosure"

Q/GDW 11882-2025 Technical Specification for Prefabricated Enclosure-Type 10kV and 35kV Switchgear Equipment

GB/T 20138-2023 "Protection Rating of Electrical Equipment Enclosures Against External Mechanical Impacts (IK Code)"

GB/T 8625 "Test Method for Flame Retardancy of Building Materials—Fire Resistance Test Methods for Building Components—Part 1: General Requirements"

GB50009 "Code for Load Design of Building Structures"

GB/T50011 "Code for Seismic Design of Buildings"

GB 50060-2008 Code for Design of High-Voltage Switchgear Installations Rated from 3 to 110 kV

 

Relevant parameters

 

Serial number

Name

Parameter

1

Cable winch

Electric, dual-wheel assembly

2

Air-suspension semi-trailer body

15000 × 3000 × 1100 / 1690

3

Switchgear enclosure

9500*3000*3200

4

Auxiliary system

Video Surveillance and Fire Alarm System

5

All-electronic multifunction energy meter

3×100V, 1.5(6)A, 0.5S, RS485 three-wire three-wire

6

Interlayer switch

22 Electricity 2 Light

7

Line Protection and Control Device

Line Protection and Control Device

8

Station Power and DC Power System Cabinet

Configure one integrated power system with a battery capacity of 65 Ah, including one cabinet for lithium batteries at 220V DC and one power distribution cabinet.

9

Bus PT cabinet

12kV

10

10kV outgoing switchgear

12 kV, 1250 A, 31.5 kV

11

10kV incoming switchgear

12 kV, 4000 A, 31.5 kV

12

Auxiliary system

Video Surveillance and Fire Alarm System

13

Recharge cabinet

Includes a 38Ah lithium battery, DC 220V, and a 3kVA inverter unit.

14

Main Transformer Protection, Measurement, and Control Device & Switchgear Cabinet

1 main transformer protection and monitoring screen; 1 set of operating host, 1 protocol conversion device, 1 monitoring host, and 1 Ethernet switch.

1 network printer, 1 GPS dual-time synchronization device, and 1 screen panel.

15

Secondary cabin body

3000*3000*2600

16

Modular hydraulic semi-trailer

15,200 × 3,000 × 1,100 / 1,690

17

Complete protection device with midline point grounding

SUN-BZFZ-110; 100-200/5 10P20

18

Main transformer

SFZ11-50000/110; 110 ± 8 × 1.25% / 10.5 kV; Ud = 10.5%; YN.d11

 

Product Message