Product Center

EPS Fire Emergency Power Supply


EPS Fire Emergency Power Supply


Product Overview

Dual-power source switching, high reliability, long service life—host lifespan exceeds 20 years.

The intelligent battery charging management function enables automatic switching between equalization and float charging, effectively extending battery life. It also features automatic monitoring of battery status and provides self-protection against overcharging and over-discharging.

It employs CPU control to ensure precise operation at each motion point, with LED display and audible alarms for clear visibility of the operating status.

Equipped with fire linkage functionality, it can achieve remote monitoring via RS232 or RS485 interface.

It features protection functions such as overvoltage, undervoltage, overtemperature, overcurrent, and short-circuit protection.

Modular design for easy maintenance.

 

Environmental conditions

 

1 Ambient temperature Not higher than +50℃ and not lower than -10℃, with the average temperature over 24 hours not exceeding +35℃.
2 Altitude Altitude not exceeding 2000m.
3 Relative humidity The daily average shall not exceed 95%, and the monthly average shall not exceed 90%.
4 Pollution Level Level III.
5   Locations free from fire hazards, explosion risks, severe contamination, chemical corrosion, and intense vibrations.
6   A place free from severe vibrations and jolts.

 

Performance parameters

 

Model Specifications LJ-EPS 2.2~22kW LJ-EPSS 25~75kW LJ-EPSS 93~500kW
Input Voltage 380VAC ±20%
Number of phases Three-phase four-wire + ground wire
Frequency 50 Hz ±10%
Output Voltage Normal operation: Same as mains voltage; Emergency operation: 380VAC ±3%.
Waveform Sine wave (THD ≤ 3%)
Frequency Normal operation: Synchronized with the utility power; Emergency operation: 50 Hz ± 0.5%
Output branch Route 1 (expandable)
Output branch type Continuous-type, Non-continuous-type, Fire-linked type
Battery Battery form Sealed and water-free
Nominal voltage 216VDC 324VDC 480VDC
Emergency standby time 90 minutes (can be adjusted as needed)
Conversion time <5s (customizable for special cases: ≤0.25s, ≤0.1s, ≤2.5ms, 0ms)
Protection function Overcharge, undervoltage, excessive humidity, overload, short circuit, overvoltage, and undervoltage protection for batteries.
Communication RS232/RS485, communication protocol: Modbus or as per customer requirements; remote monitoring card with SNMP (optional)
Overload capacity 120% of normal operation; 150% for 1 minute
Display LCD, LED (or touchscreen)
Efficiency During emergency power supply: ≥95% Normal operation: 299%
Work environment Noise (1m distance) No noise when powered by mains electricity; during emergency operation: ≤55 dB; for models above 75 kW: ≤60 dB.
Humidity 10-90% non-condensation
Temperature 20℃~40℃
Altitude ≤2000 m (>2000 m: for every additional 100 m, the power output is reduced by 1%)
Adapt to the load Suitable for inductive loads and inductive-capacitive hybrid loads.
Size/Weight See table.
Door opening method and cable entry method Front door single-opening, rear door double-opening, bottom-entry wiring (standard model)

 

Product Message